BQMS Battery Monitoring System

Manufacturer
Eagle Eye
Product Type
Monitoring

PRODUCT DESCRIPTION

The BQMS is a versatile Battery Monitoring System designed for stationary power applications. Parameters monitored include string voltage, string current, cell voltage, cell/connection resistance, cell temperature, & ambient temperature. The BQMS is designed for use on vented lead acid (VLA), valve regulated lead acid (VRLA), and nickel-cadmium (NiCad) battery systems. Optional add-on components can be included for monitoring electrolyte level and ground faults. See our complete NERC Battery Monitoring Solution for more information.

    • Measurement Range Battery Capacity: 5 – 6,000 Ah
    • System Voltage: 0 – 576 VDC
    • Unit Voltage: 2, 4, 6, 12 VDC
    • Load Current: ±10,000 A
    • Temperature: 0 – 80°C (32 – 176°F)
    • Accuracy/Resolution System Voltage: ±0.5% / 0.1 V
    • Load Current: ±2% / 0.1 A
    • Unit Voltage: ±0.5% / 0.01 V
    • Internal Resistance: ±2% / 0.001 mΩ
    • Unit Temperature: ±2% / 0.01°
    • Resistance Test Load Less than 2A AC per cell
    • Measurement Interval String voltage/current: Real-time
    • Cell voltage: 1 sec to 1 min (adjustable)
    • Resistance: 10 min to 24 hours (adjustable)
    • Communication Protocols TCP/IP to proprietary software
    • Modbus TCP
    • DNP3
    • Alarming Form C Contacts
    • Email/SMS alerts
    • Operating Environment Temperature: 0 – 65 °C (32 – 150°F)
    • Relative Humidity: Under 80%
    • Power Requirements 43 – 250 VDC
    • 110 – 220 VAC
    • Dimensions CCU: 210 x 76 x 200 mm (8.25 x 3 x 7.9 in)
    • Module: 114 x 70 x 39 mm (4.5 x 2.75 x 1.5 in)
    • True 24/7/365 monitoring with included Battery Management Software
    • Installation and maintenance can be done while battery systems are online
    • Meets IEEE and NERC standard recommendations for battery monitoring solutions
    • Utilizes a patented ripple-removing algorithm for the most precise and repeated results in any environment
    • Injects a minimal current, allowing the user to test their battery multiple times a day without adverse effects on your battery or battery monitoring system
    • Includes dry contacts for external alarming
    • Can monitor all your systems in real-time
    • Can be powered by AC or DC
New call-to-action